Skip to content

High Performance Current Sensing for Automation

High Performance
Current Sensing for Automation

1-800-959-4014 | sales@nktechnologies.com

1-800-959-4014
sales@nktechnologies.com

Current Transformer Monitoring

Designed & Assembled in the USA

Home » Current Transformer Monitoring

Current Transformer Monitoring

C.T.s (Current Transformers) have been used for many years to measure AC Current Transformer Monitoringamperage. There are many C.T.s installed throughout Electric Utilities, Process Plants and Manufacturing facilities. Typically a C.T. provides either a 1A, or more commonly a 5 Amp AC output on the secondary side. In order to use this signal for a modern control system (DCS, PLC or DDC) or Data Logging System a signal conversion or conditioner device is required to provide an analog DC signal.

C.T.s step down current and the secondary has to feed into a very low impedance to maintain accuracy. In the event that the secondary is open-circuited during operation the device operates as a step-up voltage transformer since there is nowhere for the current to flow and voltages of several kV appear on the secondary, overheating occurs and combustion or explosion often results. NK Technologies’ Split-Core Current Transducers are simply and safely snapped over the shorted secondary of a C.T. to provide a fully isolated analog 4-20mA DC signal proportional to the current in the secondary, which in turn is proportional to the measured (primary) current.

NK’s Split-core Current Transducers are used to safely monitor the secondary of high voltage C.T.s used in power generation and distribution in the low voltage cubicles.

Total 2 Votes:
0

Tell us how can we improve this post?

+ = Verify Human or Spambot ?

Please login to view this document

Don't have an account? Click to Sign Up

Forgot your password?