VFD and SCR output waveforms are rough
approximations of a sine wave. There
are numerous spikes and dips in each cycle. ATR transducers
use a mathematical algorithm called "True RMS,"
which integrates the actual waveform over time. The output is
the amperage component of the true power (heating value) of
the AC current waveform. True RMS is the only way to
accurately measure distorted AC waveforms. Select
ATR transducers for nonlinear loads or in "noisy"
power environments.
The current waveform of a typical linear
load is a pure sine wave. AT transducers measure the peaks of
these sine waves, then calculate the average amperage. This
works well on constant speed linear loads in a
"clean" power environment. Select
AT transducers for strictly linear loads on "clean"
power.
| ATR
0, 1 & 2 |
0-2 to 0-200A |
AC |
True RMS |
pdf |
Spec's |
| AT
0, 1 & 2 |
0-2 to 0-200A |
AC |
Average
sensing |
pdf
|
Spec's |
| AT/ATR
3 & 4 |
0-375 to
0-2000A |
AC |
High Current |
pdf
|
Spec's |
| ATP
0, 1 & 2 |
0-2 to 0-200A |
AC |
Powered
Transducer |
pdf
|
Spec's |
| ATP/ATPR
3 & 4 |
0-375 to 0-2000
A |
AC |
High Current
Powered Transducer |
pdf
|
Spec's |
| AP/APR
0, 1, 2, & 3 |
0-10 to 0-400A |
AC |
DIN-rail
Current Transducer |
pdf
|
Please contact NK |
| ATQ
0, 1 & 2 |
0-2 to 0-200A |
AC |
Frequency
Output |
pdf
|
Please contact NK |
| DT
0,1, 2, 3 & 4 |
0-5 to 0-400A |
DC |
Hall effect
technology |
pdf
|
Spec's |
‘ATR’ transducers from NK Technologies combine a current transformer and a True RMS signal
conditioner into a single package. The ATR Series provides
True RMS output on distorted waveforms found on VFD or SCR
outputs and on linear loads in "noisy" power
environments. Available in a solid or split core case.
- VFD Controlled Loads
VFD output indicates how the motor
and attached load are operating.
- SCR Controlled Loads
Accurate measurement of phase angle
fired or burst fired (time proportioned) SCRs. Current
measurement gives faster response than temperature
measurement.
- Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most accurate way to measure power
supply or ballast input power.
- True RMS Output
— True RMS technology is accurate on distorted waveforms
like VFD or SCR outputs.
- Jumper Selectable Ranges
— Reduces inventory.
— Eliminates zero and span pots.
- Isolation
— Output is magnetically isolated
from the input for safety.
— Eliminates insertion loss (voltage drop).
- UL, CUL and CE Approval
Accepted worldwide.
| Output Signal |
4–20mA, Loop-powered, True RMS |
| Output Limit |
23mA |
| Accuracy |
1.0% FS |
| Response Time |
600mS (to 90% step change) |
| Frequency Range |
10–400Hz |
| Power Supply |
24VDC Nominal, 40VDC Maximum |
| Isolation Voltage |
UL listed to 1,270VAC, tested to 5KV |
| Input Ranges |
Field selectable from 0–200A (see
Ordering Information). Consult factory for custom
ranges. |
| Sensing Aperture |
• FT Models: 0.75" (19mm) dia.
• SP Models: 0.85" (21.5mm) sq. |
| Case |
UL 94V-0 Flammability rated |
| Environmental |
–4 to 122°F (–20 to 50°C), 0–95%
RH, non-condensing |
| Listings |
UL 508 Industrial Control Equipment
(USA & Canada), CE (Pending) |
^ back
to top
‘AT’ Current Transducers from NK
Technologies combine a current transformer and signal
conditioner into a single package. The AT Series has jumper
selected current input ranges and industry standard 4–20mA,
0–5VDC or 0-10VDC outputs. The AT Series is designed for
application on ‘linear’ or sinusoidal AC loads. Available
in a split core case or two types of solid core cases.
- Automation Systems
Analog current reading for remote
monitoring and software alarms.
- Data Loggers
Self-powered transducer does not
drain data logger batteries.
- Panel Meters
Simple connection displays power consumption.
- Accurate
Factory matched and calibrated
single piece transducer is more accurate than traditional
two-piece field installed solutions.
- Average Responding
"Average responding"
algorithm gives a RMS output on pure sine waves. Perfect
for constant speed (linear) loads.
- Jumper Selectable Ranges
— Reduces inventory.
— Eliminates zero and span pots.
- Isolation
— Output is magnetically isolated
from the input for safety.
— Eliminates insertion loss (voltage drop).
- UL, CUL and CE Approval
Accepted worldwide.
| |
–005 Models |
–010 Models |
–420 Models |
| Output Signal |
0–5VDC |
0–10VDC |
4–20mA |
| Output Limit |
8.2VDC |
15VDC |
32mA |
| Accuracy |
1.0% FS |
1.0% FS |
1.0% FS |
Response Time
(10–90% step change) |
100mS |
100mS |
300mS |
| Frequency Range |
50–60Hz |
50–60Hz |
20–100Hz* |
| Other Frequencies |
Special calibration
available for any frequency from 10–400Hz* |
| Power Supply |
Self-powered |
Self-powered |
12–40VDC,
Loop-powered |
| Loading |
1M
W
minimum for rated accuracy
100K W add 1.3% error |
See "Power Supply" below |
| Isolation Voltage |
UL listed to 1,270VAC,
tested to 5KV |
| Input Ranges |
Field Selectable Ranges
from 0–200A (see Ordering Information). Custom ranges
available, consult factory. |
| Sensing Aperture |
• FF Case: 0.55"
(14mm) dia.
• FT Case: 0.75" (19mm) dia.
• SP Case: 0.85" (21.5mm) sq. |
| Case |
UL 94V-0 flammability
rated |
| Environmental |
–4 to 122°F (–20 to
50°C), 0–95% RH, non-condensing |
| Listings |
UL 508 Industrial Control
Equipment (USA & Canada), CE |
*For sinusoidal waveforms only. Select
ATR Transducers for distorted waveforms.
^ back
to top
'AT/ATR 3 & 4' transducers from NK
Technologies combine a high
capacity current transformer and a signal conditioner into a
single package. The AT version is Average Responding for use
on linear (sinusoidal) loads. The ATR version is True RMS
for use on distorted waveforms found in VFD or SCR outputs.
Available in a solid or split core case.
- Large Pumps
Detect dry run electronically.
- Power Generation
Measure the output of generators.
- Electric Heating Elements
— Monitors heater load.
— Faster response than temperature sensors.
- Large Aperture
Accommodates large conductors or
wire bundles.
- Select the Right Output
— True RMS technology is accurate
on distorted waveforms like VFD or SCR outputs.
— Average Responding-for linear, sinusoidal waveforms
- Three Switch Selectable Ranges
— Reduces inventory.
— Eliminates zero and span pots.
- Isolation
Magnetic isolation protects
installers and systems.
- Easy Installation
Single piece with integral mounting
brackets makes for a simple, solid installation.
- UL, CUL and CE Approval
Accepted worldwide.
| Output Signal |
4-20mA, Loop-powered |
| Output Limit |
23mA |
| Accuracy |
1.0% FS accuracy, True RMS |
| Measurement |
True RMS or Average Responding (see
Ordering Information) |
| Response Time |
500mS (to 90% of step change) |
| Frequency Range |
• ATR: 10-400Hz
• AT: 50-60Hz, Sinusoidal |
| Power Supply |
24VDC Nominal; 40VDC Maximum |
| Isolation Voltage |
600VAC |
| Input Ranges |
• AT/ATR3: 375, 500, 750A
• AT/ATR4: 1000, 1333, 2000A |
| Sensing Aperture |
3.0" (76mm) dia. |
| Case |
UL 94 Flammability rated |
| Environmental |
-4 to 122°F (-20 to 50°C), 0-95% RH,
non-condensing |
| Listings |
UL 508 Industrial Control Equipment
(USA & Canada), CE |
^ back
to top
‘ATP’ Current Transducers from NK
Technologies are a new variation of our tried and true
transducers. Self-powered sensors are the easiest to install,
but producing the industry standard 4 to 20 mA output requires
a separate power source, so there will be 4 mA when there is
zero current. The ATP Series allows the installer to use 120
VAC to power the sensor, with other models configured to use
24 VAC or VDC. NK can provide models producing industry
standard 4–20mA, 0–5VDC or 0-10VDC outputs. The response
times are faster and accuracy higher than our self-powered
models. All have the jumper or switch (high current models) to
select the range closest to the actual load, providing for the
best resolution.
- Automation Systems
Analog current reading for remote monitoring and software
alarms.
- Data Loggers
Self-powered transducer does not drain data logger
batteries.
- Panel Meters
Simple connection displays power consumption.
- Accurate
Solid core models 1.0% FS, and
- Average Responding
"Average responding" algorithm gives a RMS
output on pure sine waves. Perfect for constant speed
(linear) loads.
- True RMS
—Available from models with ranges 0-375 amps and higher
- Jumper Selectable Ranges
— Reduces inventory.
— Eliminates zero and span pots.
- Isolation
— Output is magnetically isolated from the input for
safety.
— Eliminates insertion loss (voltage drop).
- UL, CUL and CE Approval
Accepted worldwide.
| |
–005 Models |
–010 Models |
–420 Models |
| Output Signal |
0–5VDC |
0–10VDC |
4–20mA |
| Output Limit |
5.6 VDC |
11.2 VDC |
22.4 mA |
| Accuracy (Split Core) |
1.0% FS |
1.0% FS |
1.0% FS |
| Accuracy (Solid Core) |
0.5% FS |
0.5% FS |
0.5% FS |
| Accuracy (Large Case) |
1.0% FS |
1.0% FS |
1.0% FS |
Response Time
(10–90% step change) |
100mS |
100mS |
100mS |
| Frequency Range |
40–100Hz* |
40–100Hz* |
40–100Hz* |
| Other Frequencies |
Special calibration
available for any frequency from 10–400Hz |
| Power Supply
(2VA max) |
120VAC or 24VAC/DC |
120VAC or 24VAC/DC |
120VAC or 24VAC/DC |
| Loading |
25K W
minimum for rated accuracy |
500 W maximum |
| Isolation Voltage |
Tested to 5KV |
| Input Ranges |
Field Selectable Ranges
from 0–2000A (see Ordering Information). Custom ranges
available, consult factory. |
| Sensing Aperture |
• FF Case: 0.55"
(14mm) dia.
• FL Case: 3.00"(76.2mm) dia.
• SP Case: 0.85" (21.5mm) sq. |
| Case |
UL 94V-0 flammability
rated |
| Environmental |
–4 to 122°F (–20 to
50°C), 0–95% RH, non-condensing |
| Listings |
UL 508 Industrial Control
Equipment (USA & Canada), CE (pending) |
*For sinusoidal waveforms only. Select
ATPR Transducers for distorted waveforms.
'DT' Current Transducers from NK
Technologies combine a Hall effect
sensor and signal conditioner into a single package. The DT
Series has jumper selectable current input ranges and industry
standard 0-20mA, 4-20mA, 0-3VDC, 0-5VDC or 0-10VDC outputs.
Available in a split core package.
- Battery Banks
— Monitors load current.
— Monitors charging current.
— Verifies operation.
- Transportation
Measures traction power or auxiliary loads.
- Electric Heating Elements
Faster response than temperature sensors.
- Three Jumper Selectable Ranges
— Reduces inventory.
— Eliminates zero and span pots.
- Isolation
— Output is magnetically isolated from the input for
safety.
— Eliminates insertion loss (voltage drop).
- Internal Power Regulation
— Works well, even with unregulated power.
— Cuts installation costs.
- Easy Installation
Split core design with built-in mounting brackets makes
installation a snap.
| Output Signal |
0-20mA, 4-20mA, 0-3VDC, 0-5VDC or
0-10VDC |
| Output Limit |
• 0–20mA, 4–20mA: 23mA
• 0–3VDC: 3.5VDC
• 0–5VDC: 5.75VDC
• 0–10VDC: 11.5VDC |
| Accuracy |
2.0% FS split core,
1% FS solid core |
| Repeatability |
1.0% FS |
| Response Time |
100mS (to 90% of step change) Split
Core
20mS (to 90%
of step change) Solid Core
|
| Frequency Range |
DC |
| Power Supply |
20–50VDC, 22–38VAC. Power input
and output signal are not isolated. 120VAC available in
solid core designs only (maximum
range 200 A) |
| Power Consumption |
2VA |
| Loading |
• 0–20mA, 4–20mA:
500 W
maximum
• 0–3/5/10VDC: 25K W for rated accuracy |
| Isolation Voltage |
3kV (monitored line to output) |
| Linearity |
0.75% FS |
| Current Ranges |
Field Selectable Ranges from 0–400A
(see Ordering Information) |
| Sensing Aperture |
0.85" (21.5mm) sq. split core,
0.75" (19.1mm) solid core |
| Case |
UL 94V-0 Flammability rated |
| Environmental |
–4 to 122°F (–20 to 50°C), 0–95%
RH, non-condensing |
^ back to top