AG Series
sensors from NK Technologies protect
people, products and processes from ground faults by
monitoring all current-carrying wires in grounded single or
3-phase systems.
Operating Principle: Under normal conditions, the current in the hot leg
of a two-wire load is equal in strength but opposite in sign
to the current in the neutral leg. These two currents create
magnetic fields that are also equal but opposite. When
conditions are normal, the fields cancel, producing a
"Zero Sum Current". If any current leaks to ground
from one wire (Ground Fault), the two currents become
imbalanced and the result is a net magnetic flux or field. AG
Series ground fault sensors monitor this field and alarm when
leakage rises above setpoint. This concept applies to grounded
3-phase delta and wye systems.
- Operation to Match Your Application:
Latching Output
stays in tripped condition even if fault has cleared
- Auto-Reset Output
returns to shelf-state condition when fault clears
- Setpoint Options to Match Your Needs:
Tri-Set Field
select 5, 10 or 30mA. Fast and convenient. (AG3 only)
Single-Set Factory
adjusted setpoint. Specify 5100mA (AG1) or 80950mA
(AG2) when ordering.
- Compatible with Standard Equipment
Works on 1F or 3F power. Controls standard shunt trip
breakers or contactors. Tie into Emergency Circuits (EMO/EPO).
- Isolated
Magnetically isolated from the monitored circuit and
control power
- UL and CE Approval
Accepted worldwide.
Applications
- Personnel Protection (typically 5mA)
Senses low fault currents and alarms to shut power before
injury occurs.
- Equipment Protection (typically 30mA)
When personal protection is not an issue, select a higher
setpoint to protect equipment or product.
- General Use Sensor will trip at
the pre-determined fault current level, allowing for
design options:
1] Immediately operate shunt trip breaker or contactor coil,
de-energizing the offending circuit
2] Provide alarm so the offending circuit can be repaired when
convenient
3] Alarm & latch, so repairs can be scheduled, and the
fault can be located easily even if it clears
- Regulatory Approval
Meet requirements by industry groups and governments for
Ground Fault Protection.
Specifications
| Setpoint
Range |
|
|
Factory adjusted and
sealed (field adjustment possible) |
| AG1: 5100mA,
specify when ordering |
| AG2: 80950mA,
specify when ordering |
|
|
AG3: 5, 10 & 30mA
jumper select |
| Output |
Isolated dry contact
(solid state or relay, see Ordering Information) |
| Output Rating |
Solid State AC Switch:
1A @ 240VAC
Solid State DC Switch: 0.15A 30VDC
Relay: 1A @ 125VAC, 2A @VDC |
| Off State Leakage |
<10 microamps NO solid
state, |
| Response Time |
200mS @ 5% above
setpoint
60mS @ 50% above setpoint
15mS @ 500% above setpoint |
| Isolation Voltage |
Up to 1,250VAC (monitored
circuit) |
| Frequency Range |
50400Hz (monitored
circuit) |
| Sensing Aperture |
0.75" (19mm) dia., up
to 4" (100mm) dia. available, consult factory. |
| Power Supply |
120 VAC , 50-400Hz,
operates from 55110% of nominal voltage
24VAC & 24VDC, operates +/10%
Green LED = power (all models) |
| Case |
UL 94V-O Flammability
rated |
| Environmental |
5 to 158°F (15 to
70°C), 0-95% RH, non-condensing |
| Safety |
UL 1053, Class 1
Recognized, CE* |
*Most option combinations are UL recognized.
| Normally Energized Models (FS
Option solid
state output) |
| Protection
from faults and loss of control power. |
Control Power Applied
|
| No Power |
No Fault |
Fault |
| N.C. Normally Closed |
Closed |
Open |
Closed |
| N.O. Normally Open |
Open |
Closed |
Open |
| Normally De-energized Models (NF
Option solid state output) |
| Protection
from faults only when control power is applied. |
Control Power Applied
|
| No Power |
No Fault |
Fault |
| N.C. Normally Closed |
Closed |
Closed |
Open |
| N.O. Normally Open |
Open |
Open |
Closed |
|
| Normally Energized Models (ENE Option relay output) |
| Protection
from faults and loss of control power. |
Control
Power Applied |
| No Power |
No Fault |
Fault |
| N.C. Normally Closed |
Closed |
Open |
Closed |
| N.O. Normally Open |
Open |
Closed |
Open |
| Normally
De-energized Models (DEN Option relay
output) |
| Protection
from faults only when control power is applied. |
Control
Power Applied |
| No Power |
No Fault |
Fault |
| N.C. Normally Closed |
Closed |
Closed |
Open |
| N.O. Normally Open |
Open |
Open |
Closed |
| |
| Latching (LA
Option) |
Latching models initially power up in
the Reset position. If there is a fault or the test
button is pressed, the output switches and is latched.
The output will remain latched after the fault is
cleared, even if control power is removed. To reset
the output, apply a momentary contact across the
"Reset" terminals (56).
|
| Optional Electrical Noise Immunity
Available for Relay Output Models (-N suffix) |
|
RGCS Ultra
fast, residual current sensor |
Control Power Applied |
| This is a new
sensor, developed so the OEM user can achieve UL943A
recognition of their control panels. This sensor trips
so fast, that it can be used with most circuit breakers,
and the total latency time to trip will be shorter that
UL requires. The sensor will have to be tested with each
circuit breaker individually. Please contact the factory
for more information. |
No Power |
No Fault |
Fault |
| Open |
Open |
Closed |