Skip to content

2020 & 2023 NEC Impact to the Market – Commercial Kitchens

Designed & Assembled in the USA

Home » LP » 2020 & 2023 NEC Impact to the Market – Commercial Kitchens

The 2020 and 2023 editions of the National Electric Code (NEC) section 210.8 (B) have expanded GFCI regulations in areas with sink and permanent provisions for food preparation and cooking, directly affecting commercial kitchens. The updated code covers GFCI protection for personnel in “other than dwelling” units and focuses on GFCI protection for applicable kitchen appliances powered by 3-phase power (e.g. line to line, < 250 VAC, 208 VAC typical). However, ideal GFCI solution would also be compatible with 2-pole (e.g. line to line, 240 VAC).

Both 2020 and 2023 NEC have increased GFCI requirements in more locations. What this means to architects, designers, electricians, general contractors, or program managers is a year over year increase in demand for breakers with GFCI protection. Will manufacturers of breakers continue to struggle servicing the demand for 15 A to 100 A, 2 or 3 pole, GFCI MCB’s?

Summary of 2023 Code Changes

2023 Edition NEC article 210.8 (B) related to spaces “other than dwellings” has been rewritten to clarify and expand GFCI requirements.

  • a)

    The word “Kitchens” was added as article 210.8(B)(2) and requires all single phase (50A or less) or 3 phase (100A or less) plug-incord-connected appliances to have GFCI protection.

  • b)

    A new addition, article 210.8(B)(4), covers buffet serving areas, commonly referred to as break areas within commercial occupancy. The effected spaces include areas with provisions for food service. beverage service, or cooking. Any receptacles and special appliances within these areas shall be GFCI protected.

  • c)

    The specific appliances list was updated (article 210.8(D)(8) through (12)) for appliances that are commonly installed as hardwired outlets, 60A or less. Shock hazards exist whether appliances are energized from outlet (hardwired) or receptacle (cord and plug).

  • d)

    A new code (Stationary appliances, article 210.8(B)(7)) revised the code to include stationary appliances located within 1.8 m (6 ft) of the top inside edge of a sink shall have GFCI protection.

A 5 mA Ground Fault Protection System

Many GFCI solutions exist for low amperage (15/20A) single-phase branch circuits, often in the form of an “all-in-one” GFCI Circuit Breaker. The situation changes when moving to three-phase power. GFCI protection for a three-phase branch circuit typically requires a shunt trip circuit breaker combined with a ground fault relay. This is especially true when the amperage is 60A or higher, where a shunt trip circuit breaker with ground fault relay is the only solution.

A 5 mA ground fault protection system includes a breaker with shunt trip option and an AC ground fault sensor. All NK Technologies ground fault relays have numerous options to ensure compatibility with any shunt trip breaker (MCB or MCCB), relay or contactor. NK Technologies ground fault sensors are compact in size and easily installed within the panelboard. A shunt trip breaker with ground fault sensor will protect 15 A to 100+ A branch circuits from both overload current and ground fault currents exceeding 5 mA.

When combined with a shunt trip breaker, the AGU Series is a cost effective, compact ground fault protection system that is easy to install and set up, and is compatible across all OEM panel boards. The AGU Series ground fault sensor can service the NEC GFCI requirements for up to 50 A single phase (120 VAC to 240 VAC) or up to 100 A three-phase (208 VAC or 240 VAC) branch circuit. For situations when the wire bundle is larger than 0.75” diameter, use the AGL Series instead.

This is the NK Technologies AGU-Series Ground Fault Relay.
5 mA Ground Fault Solutions for Single or 3-Phase up to 100Amps

Resources & Downloads

Contact Us for Assistance

"*" indicates required fields

Name*
Do you have concerns about ground fault protection*
Privacy Policy and Data Usage Policy Acknowledgment*
* required field
Hidden
This field is for validation purposes and should be left unchanged.

Need Help? Contact one of our commercial kitchen specialists.

1-800-959-4014

Here is what Engineers have to say about our technical expertise...

“Changes to NEC 210.8 B-F have challenged all of us in the industry to find new GFCI solutions. When NK Technologies reached out to us recently, we decided to invest a few hours into meeting with their application experts. Five of our electrical engineering designers attended the session and considered it time well spent. NK Technologies has an in-depth understanding of the new NEC requirements and ground fault products designed to meet them. We are thankful for their time.”

PK Electrical
One of the top electrical and low voltage/communications design firms,
in both the private and public sectors, based in Reno, NV and Denver, CO.

Please login to view this document

Don't have an account? Click to Sign Up

Forgot your password?